HW group Expander 4xDI 1W-UNI
Expansion module for connecting dry contacts
- Input: 4x dry contact input – any detector (e.g. door contact) can be connected
- Interface: 1-Wire UNI (2x RJ11 for daisy-chaining)
- Connects to: Poseidon 2250, 4002, Ares 12/14, Poseidon2
- Power: Bus-powered (1-Wire UNI) or external 5V adapter
- Environment: Indoor use
Expansion module for connecting 4 dry contact inputs to Ares and Poseidon units.
Connect another button, door contact, smoke detector etc. to the 1-Wire UNI bus (RJ11).
Connect four digital sensors (detectors) to Poseidon and Ares units. The expander is connected using a single RJ11 cable. Several Expanders can be daisy-chained. Supplied with a 3m RJ11 cable.
- Expander can be combined with other sensors on the bus (temperature, humidity, light intensity, current, ...).
- Alarms can be configured for each dry contact input in the Ares or Poseidon unit.
(Normally Open / Normally Closed)
- The Expander module is powered from the Ares / Poseidon unit.
Dry contact inputs are electrically connected to the Ares / Poseidon unit.
Bus | |
Type | 1-Wire UNI |
Supported by | Ares, Poseidon2, Poseidon 2250, 4002 |
Sensors occupation | Expander unit reserves 4 sensor positions from the 1-Wire bus limit. Even if you use only 2 external DI, Expander unit blocks 4 sensors positions. |
Connector | 2x RJ11 (bus input & bus output for next sensor) |
Power | Powered by RJ11 bus, in some cases external 5V power adapter is required. |
Power limitation | Max 2 Expander units can be connected to one Active port (Poseidon or Ares RJ11 plug) To boost-up the power, use external 5V power adaptor or “1-Wire hub Power” |
Max distance | 60 m total cable length from the Active port of the Poseidon / Ares unit |
Accessories | Delivered with 3m cable 2x RJ11 included. |
4x Digital Input | |
Port | IN1 –IN4 |
Type | Digital Input (supports NO/NC Dry Contact) |
Sensitivity | 1 (On) = 0-500 Ω (COM pin is connected to GND of 1-Wire UNI bus) |
Sampling period | DI state is refreshed once per second |
Galvanic isolation | Digital Inputs are NOT electrically isolated from the 1-Wire UNI bus |
Physical parameters | |
Operating conditions | -40 to +85 °C (-40 to185 °F) / 5 to 90 % relative humidity |
Dimensions / Mass | 65 x 80 x 30 [mm] / 70 g |
Expander-4xDI 1W-UNI
Expander 4xDI 1W-UNI Industrial
- 4 dry contact inputs, expander-sensor, RJ11.
Connect up to 4 dry contacts. 1-Wire UNI (RJ11), compatible with Ares and Poseidon2.