HW group PowerEgg2
110/230V power detection and switching
- 110 to 230 VAC mains voltage detection
- Mains power failure is indicated with a relay contact
- Electrically isolated output contact
- Output control
- Pass-through mode when the control voltage / contact is not connected (Power output = Power Input)
- Electrically isolated control input
- Control voltage 3V or more, or a closed contact
PowerEgg2 combines two functions in one device -power Detector & Control. Detector indicate failures of electricity supply (110/230V, single phase) by relay output. Power Control can switch Off/On power supply output 8A, it´s controlled with a low voltage input. The PowerEgg can be connected to any device with digital inputs (DI) and digital outputs (DO).
PowerEggPowerEgg2 is a "pass-through mains outlet" with two IEC-320 connectors – a plug (C14) at the input, and a socket (C13) at the output.
PowerEgg2 combines two functions in a single device
- DETECTOR:
Detects the presence of mains voltage at the input (indication with a change-over contact)
- CONTROL:
Disconnects the output voltage (control with external DC voltage or a contact)
Applications
- Detection of power supply on the input, Switch off output voltage
- Alarm activation upon supply voltage / phase failure
- Voltage monitoring at UPS input/output
- Remote server restart
- Switching on additional cooling or ventilation
- Partial disconnection of the load when running on battery power
Specifications
- Input voltage:
- 3–12V –control voltage input:
voltage range 3V (5 mA) to 12V (20mA)
- DRY –external contact connection:
<100Ohm / max 3mA
- Output control logic:
Application of external voltage disconnects the output
- Output state when control voltage applied:
Power circuit is interrupted - Input voltage presence indication:
Relay activated (NO connected to COM) - Detector relay parameters:
120V / 0,5A AC, 60V / 0,3A DC, 24V / 1A DC
110V to 250V AC –IEC-320 C14
Power output current:
max. 8A –IEC-320 C13
Output control:
Application of external voltage to the “CONTROL” input
Input voltage detection:
Double-throw relay contact
Operational/storage temperature:
-20°C to 80°C
Dimensions:
125 x 55 x 40mm
Ordering
- PowerEgg2
- Detects external AC voltage, controlled AC output