Product Change Notification - PCN 001093
January 10, 2025

SPHINX in Europa
DE
  • AT
  • BE
  • DK
  • FR
  • DE
  • IE
  • IT
  • NL
  • PL
  • ES
  • SE
  • CH
  • UK
Produktänderungen > Product Change Notification - PCN 001093
January 10, 2025
MOXA

Product Change Notification - PCN 001093
January 10, 2025

We would like to inform you that Moxa is going to make changes to the MGate 5121 Series, MGate 5122 Series, and MGate 5123 Series.



These changes will be available for download by January 15, 2025.

Please review the details below to determine how these changes will affect your products and/or operations.





What will change?


The following changes will be implemented on the new firmware versions:

Current Firmware Version New Firmware Version (V2.0)
Supports CANopen or J1939
  1. New protocol: Supports Proprietary CAN (CAN 2.0A/B)
  2. CANopen enhancement features:
    • Initial Slave Parameters via MGate
      Some CANopen slave devices don't provide utility to configure its PDO parameters or communication parameters. Firmware version 2.0 supports a new feature to set a user-defined value for the parameter and it will be set via SDO command when booting up and CAN bus is ready for SDO communication.
    • Intuitive PDO Configuration
      The COB ID is generated automatically with slave ID and PDO number; no need to check COB ID table by user.
      Also, quick mapping by selecting parameters from the slave EDS file.
    • Fault Protection for CANopen and Proprietary CAN (CAN 2.0 A/B)
    • Data Endian Swap for CANopen and Proprietary CAN (CAN 2.0 A/B)
      Swapping the data. The item may change with different tag types or lengths for raw data type.
      None: No swap
      Byte swap: Switch the order of bytes.
      0x11 22 33 44 55 66 77 88 -> 0x22 11 44 33 66 55 88 77
      Reverse: Reverse the order of bytes.
      0x11 22 33 44 55 66 77 88 -> 0x88 77 66 55 44 33 22 11
      Reverse with byte swap: Reverse the order of bytes first; then, switch the order of bytes.
      0x11 22 33 44 55 66 77 88 -> 0x77 88 55 66 33 44 11 22
    • Fast Object Search in CANopen Diagnostics
    • CANopen ID Change Default From 1 to 127
      Most CAN devices use lower Node ID. So this version adjusts the MGate default ID to 127 to avoid changing the MGate ID every time.
    • CANopen/Proprietary CAN(CAN 2.0A/B) Initial Delay Time
      To allow more flexibility with some legacy CAN devices, which take more time to boot up.




Which products will be affected?


Product Name Current Firmware Version New Firmware Version
MGate 5121 Series    V1.0.0 V2.0.0
MGate 5122 Series V1.0.0 V2.0.0
MGate 5123 Series V1.0.0 V2.0.0




When will the new firmware versions be available?


Product Name New Version Available for download
MGate 5121 Series V2.0.0 By January 15, 2025
https://www.moxa.com/en/products/industrial-edge-connectivity/protocol-gateways/modbus-tcp-gateways/mgate-5121-series#resources
MGate 5122 Series V2.0.0 By January 15, 2025
https://www.moxa.com/en/products/industrial-edge-connectivity/protocol-gateways/ethernet-ip-gateways/mgate-5122-series#resources
MGate 5123 Series V2.0.0 By January 15, 2025
https://www.moxa.com/en/products/industrial-edge-connectivity/protocol-gateways/profinet-gateways/mgate-5123-series#resources




If you have any questions, please contact KS Hsu at ks.hsu@moxa.com,
or contact your regional sales representative.