HW group Poseidon S-Hub

Splitter for up to 8 sensors to RS-485 bus (8+1x RJ45)

HW group Poseidon S-Hub
5139_16369.png
5139_11952.jpg
5139_11954.jpg
5139_11955.gif
5139_11956.gif
5139_11957.gif
5139_11958.gif
5139_11959.gif
5139_11960.jpg
  • BeschreibungBeschreibung
  • Weitere InformationenWeitere Informationen

S-Hub represents a device which allows connecting RS-485 sensors to Poseidon Family units. The RS-485 bus is connected to the Poseidon model 1250 via TP cables and RJ45 connectors. S-Hub allows connecting up to 8 sensors over RJ45 to a single Poseidon unit. S-Hubs can be connected in series. Though S-Hub´s topology can be found similar to Hub on Ethernet it cannot be commuted.

The RS-485 bus works reliably even over long distances in industrial environment but some principles must be obeyed when making a connection. To make sensor connection easier we supply the S-Hub along with the Poseidon. That is really a great help when it comes to installing sensors.
Standard TP cables in the star connection can be used.

Advantages of using S-Hub for RS-485 sensors´ connection:

  • Simplification of cabling (mainly in larger installations)
  • Using popular RJ45 sensors
  • Easy extension with more sensors
  • Simplified power supply connection for individual sensors. Power supply is connected directly to the S-Hub unit. It is possible to use standard power adaptor.



ProdGrafik

Connecting sensors over RS-485

Generally, the sensors communicating over RS-485 bus can be connected in serial connection or, using S-Hub, in star topology.

Line topology
For this connection you don´t need an S-Hub. The individual sensors are interconnected directly. Sometimes this connection is called a Daisy chain. It is sufficient for large buildings and long distances.

  • Connection via 4 wires (for RS-485 we recommend twisted pair)
  • Full wiring length cannot exceed 1000 meters
  • For more than 3 sensors it is necessary to increase power supply of these sensors
  • The last sensor must have the RS-485 line terminator turned on (option "LAST")



Connection with S-Hub

All sensors are connected in one place, working with RJ45 connectors only, S-Hub is located in the centre of the structure.

Principles for using S-Hub

  • Connecting with four-pair TP cables
  • Full wiring length (sum of all RS-485 cables) cannot exceed 500 meters
  • Sensors must be connected to the S-Hub subsequently from port 1 to 8 without empty slots between sensors. See picture
  • For connection of more than 3 sensors or longer wiring we recommend connecting power supply of the sensors via S-Hub as depicted above. The LED signalizes power supply from the RS-485 input (green light), or external power supply connected to the unit (red light).
  • The jumpers of the last sensor must be set to "LAST" position, all others set to "MIDDLE".



What to do when the RS-485 bus does not work

If you don´t use connection using the S-Hub and original supplied connectors, you can encounter problems with some sensors or the whole sensor network. When problems appear, check the following:

  • Check whether it all works on a table, within short distance and in ideal conditions.
  • Check sensors´ IP address configuration if several sensors do not work properly, more sensors cannot use one same address.
  • Wiring with length of more than several meters must be terminated so check the termination resistance on the last sensor or if a jumper or a DIP switch has TERM=ON.
  • The RS-485 conductors must be differentiated. Check whether A wire leads to pin A, B wire to pin B. In an idle state the voltage of the A should be a little higher than of the B one.
  • When using TP cables (RJ45), note that all sensors have the green cable connected with the white stripe cable (white-blue). Check this connection on all cables where the B-Cables weren´t used.
  • If using additional power supply for the sensors, use a galvanicaly insulated source. Sensors have little power consumtion so it is possible to lead the power over TP cable for tens and even hundreds of meters.



Ordering

Poseidon S-Hub Splitter for up to 8 sensors to RS-485 bus (8+1x RJ45)
Poseidon B-Cable RS-485 converter from 4 terminal pins (A, B, +, - ) to conector RJ45
Sensor RJ45 MIDDLE cable Connection RS-485 cable 0.5m. RJ45/4 pins to terminal block (A, B, +, - ). (3 pairs)
Sensor RJ45 LAST cable Connection RS-485 cable 0.5m.
Use for last one or single sensor on the bus (2 pairs). RJ45/4 pins to terminal block (A, B, +, - ).