HW group Spider
active converter between RS-485 and 1-Wire bus.







- Up to 4 Spiders to one Poseidon 2250
- 2x RJ45 connectors for connecting the RS-485 bus enable daisy-chaining.
- Inputs 1 to 4 support:
- Dry Contact (relay output) (RJ11)
- 1-Wire temperature sensor (RJ11)
- 1-Wire humidity sensor (RJ11)
- Power over 485 bus from Poseidon, or from external power supply (barrel connector for external 12V adapter).
- DIP switch for setting the address on RS-485 bus (sensor ID)
- Signalization of sensor value being read / dry contact switched
- Reaction to extremely short dry contact pulses (30 ms).
Spider is an active converter between RS-485 and 1-Wire bus. Connects four input sensors (dry contacts or 1-Wire bus) to Poseidon by the RS-485 bus. Spider units can be daisy chain connected.
Spider makes it easier to connect more sensors over longer distances using the RS-485 bus. Suitable for applications in rooms and larger areas.
- Up to 4 Spider units can be connected to one Poseidon model 2250.
- With Spider and S-Hub units it is easy to create flexible installations with up to 50 sensors.
- Four RJ11 inputs support these sensors:
- Temp-1Wire (1m / 3m / 10m / Outdoor / Temp-Rack19 / HTemp-Rack19)
- Humid-1Wire (1m / 3m / 10m / HTemp-Rack19)
- Input for Dry Contact (Flood / smoke and gasses / voltage and current / motion and position detectors)

Application examples
- Detection of system voltage, UPS function detection, Voltage failure alarm activation, On/Off control, Device restart
- Enlarging the number of inputs for connection of dry contacts for Poseidon 2250.
- Gathering values from 19” racks, RS-485 bus runs along the wall.
- Temperature monitoring in supermarket freezers, RS-485 bus runs along the wall behind the freezers
Input
- 4x 1-Wire probe (temperature or humidity)
6 values (at most 2 combined temp/humidity probes can be connected) - 4x dry contact
Output
- RS-485 bus –RJ45 (includes power)
- Poseidon 2250 supports up to 26 probes or 4 Spider units in total
- An extra power supply adapter is required to connect two or more Spiders
- The RS-485 communication bus can be up to 1200m (4000ft) long
- The last sensor on the RS-485 bus (at the end of the line) must terminate the bus
(“Bus Mode” jumpers set to LAST)
Ordering
| 600 273 | Spider | Connects 4 dry contacts or 1W bus RJ12 sensors to Poseidon RS-485 (RJ45) bus |