Raritan PX3-1502N-E2M5
Monitored rack power distribution unit
(0U [vertical], 7.4kVA, 24 outlets)
Monitored rack power distribution unit (0U [vertical], 7.4kVA, 24 outlets).
INPUT:
230v, 32a - Hardwired [Unterminated Cord, No Plug];
OUTPUT:
16@ C13 Locking, 8@ C19 Locking outlets;
on 2@ 1-pole, 16a Overcurrent Protectors;
FEATURES:
Billing-Grade (+/- 1%) Energy Metering [kW, kVA, V, A, Power Factor] - per inlet, per breaker/fuse;
Color, matrix LCD display : Voltage, current, or active power (per line or per breaker);
Alarms;
Configuration information (name, ratings, IP / Networking).;
Field-Replaceable, hot-swappable network module with 400MHz processor, 16MB NOR Flash, and 64MB SDRAM;
(10/100) Ethernet portRemote network monitoring via HTML, JSON-RPC, SSH, Telnet, MODBUS/TCP, and SNMPv3.
Environmental monitoring [temp/humidity] capable of up to 32 sensors.
Individual outlet numbers labeled on chassis.
Automated deployment via TFTP, DHCP/PXE, SSH(CLI), or USB Flash Drives.
WiFi Capable.
USB Webcam Capable.
iPad/iPhone/Android App.
Breaker metering and alarming (0V detection).
Max Dimensions 52mm x 55mm x 1539mm (2.1in x 2.2in x 60.6in).
Max Weight 5.5 kg.
Maximum ambient temperature 60C at full load.
Features
- Energy Metering
Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor
Metering Accuracy
ISO/IEC 62053-21 1%
Remote Outlet Switching
No
Metering per input line
Yes for all models
Metering per Branch Circuit Breaker
Yes
Environmental Sensor Ready
Yes
Compatible Sensors
Temperature, Humidity, Air Flow, Differential Pressure, Water Leak, and Contact Closure.
Cascading
Yes, Max 16 PDUs can be daisy chained using a USB connection.
Note: Firmware version 3.3.10 or above is required.
Networking
10/100/1000 BaseT Ethernet.
Optional WiFi (802.11a/b/g/n).
Onboard Display
Color, matrix LCD display : Voltage, current, or active power (per line or per breaker);
Alarms;
Configuration information (name, ratings, IP / Networking information).
Auto-flip orientation
Specifications
- Input
- Input Plug
Cord (N/A)
Nominal Voltage
230V
Maximum Input Current
32A
Rated Input Current
32A
Power Capacity
7.4kVA
Cord Length
3m
Output
- Nominal Voltage
230V
Receptacles (Output Connections)
(16) IEC320 C13 Locking
(8) IEC320 C19 Locking
Overload Protection
(2) LEGBXA6-16
Physical
- Dimensions (WxDxH)
2.1in x 2.2in x 60.6in;
52mm x 55mm x 1539mm
Unit Weight
5.5 kg
Shipping Weight
7.5 kg
Shipping Dimensions
280mm x 115mm x 1655mm
Mounting
RACK-KIT-PX2-1K-ZU
Environmental
- Operating Temperature/Environment
60 C
Operating Relative Humidity
85%
Operating Elevation
0-10000ft
Conformance
- Regulatory Approvals
CE